Calculator

What size heat pump do I need?

Your home's age, floor area and EPC band give a size and an installed cost, and what the £7,500 Boiler Upgrade Scheme grant takes off where you qualify.

Your answer

About — kW

Heat loss (design)
— W
Typical installed cost
£—–£—
BUS grant
£—
Net cost after grant
£—–£—

How the sizing works

Heat pump capacity is sized to the property's design heat loss — the rate at which the building loses heat at the coldest outside temperature you typically see. For the UK that's roughly -3°C external against 21°C internal. The kW figure on the unit needs to match or slightly exceed the heat loss, with a small margin for hot water and recovery from setback.

Heat loss by property age

Older properties lose heat faster because fabric efficiency was lower when they were built. Pre-1900 solid wall homes lose around 100 W/m² of floor area at design conditions. Post-2003 builds, with cavity wall insulation, double or triple glazing, and good loft insulation as standard, lose around 35 W/m². The calculator applies the band you select, then modifies by your current EPC.

EPC band as a heat loss modifier

Two homes of the same age and size can have very different heat losses depending on how the fabric has been maintained or upgraded. A pre-1930 detached at EPC C (good loft insulation, modern double glazing, cavity insulation added) loses materially less heat than the same property at EPC E. The calculator adjusts the baseline by your current band — improving your EPC before installing the heat pump reduces the kW you need and improves running costs.

BUS grant eligibility

The Boiler Upgrade Scheme (BUS) gives £7,500 off the installed cost of an air source heat pump (or £7,500 for ground source), or £9,000 for either if the property has no mains gas connection and is heated by oil or LPG, for applications made from 21 July 2026 to 31 March 2027; the calculator applies the £9,000 when you answer No to the mains gas question. It covers England and Wales only. To be eligible you must own the property (a landlord counts; a tenant does not) and be replacing a fossil fuel heating system (gas, oil, LPG, electric); social housing is excluded. The work is done by an MCS-certified installer, who claims the grant on your behalf and takes it off the quote. An EPC is no longer part of it — the requirement for a valid EPC with no outstanding loft or cavity wall insulation recommendations was removed on 28 April 2026. Insulation still affects how well a heat pump performs, and an installer will raise it, but it is not a condition of the grant. Applications close 31 December 2029.

What this calculator doesn't do

The figure here is indicative. A proper installer survey runs a full room-by-room heat loss calculation (sometimes called an MCS heat loss calculation), checks radiator/emitter compatibility, sizes the hot water cylinder, and considers electrical supply capacity. Use this as a starting point before requesting installer quotes.

Heat pump sizes by home type and age

Each figure is what the calculator above returns for a typical home at EPC D, which is also its "I don't know" setting. The floor areas are the ones it suggests.

Recommended heat pump capacity (kW) at EPC D
Built 50 m²
1-bed flat
70 m²
2-bed terrace
90 m²
3-bed semi
140 m²
4-bed detached
Pre-1900 6.58.511.017.0
1900–1929 6.08.510.516.5
1930–1949 5.07.09.014.0
1950–1966 5.06.58.513.0
1967–1975 4.06.07.511.5
1976–1982 3.55.06.09.5
1983–1990 3.54.55.58.5
1991–2002 3.04.05.08.0
2003 onwards 3.0*3.04.06.0

Figures include the calculator's 10% margin, round up to the next 0.5 kW, and do not go below 3 kW (* marks where that minimum sets the figure). A survey sizes to the measured load.

The same homes at EPC C
Recommended heat pump capacity (kW) at EPC C (factor 1.00)
Built 50 m²70 m²90 m²140 m²
Pre-1900 5.58.010.015.5
1900–1929 5.57.59.515.0
1930–1949 4.56.58.012.5
1950–1966 4.56.07.512.0
1967–1975 4.05.56.510.5
1976–1982 3.54.55.58.5
1983–1990 3.04.05.08.0
1991–2002 3.0*3.54.57.0
2003 onwards 3.0*3.03.55.5
The same homes at EPC E
Recommended heat pump capacity (kW) at EPC E (factor 1.20)
Built 50 m²70 m²90 m²140 m²
Pre-1900 7.09.512.018.5
1900–1929 6.59.011.518.0
1930–1949 5.57.510.015.0
1950–1966 5.07.09.014.0
1967–1975 4.56.58.012.5
1976–1982 4.05.57.010.5
1983–1990 3.55.06.09.5
1991–2002 3.04.55.58.5
2003 onwards 3.0*3.54.56.5

Many homes are bigger: in the English Housing Survey the average four-bedroom detached house in England measured between 148 m² and 233 m² depending on when it was built (Floor Space in English Homes, 2012 data), against an average home of 94 m² (2018-19). Enter your own floor area above.

Of the 30,516 air-to-water heat pump grants paid under the Boiler Upgrade Scheme (England and Wales) in 2025/26 with a recorded capacity, 81.0% were 4–12 kW and the middle install was 8–10 kW (DESNZ).

Is a bigger heat pump better?

No. MIS 3005-D, the MCS heat pump design standard (Issue 2.0, December 2024), requires a heat pump that provides at least 100% of the calculated heat load at the system's flow temperature, with no electric top-up. In England, Approved Document L adds that systems "should not be significantly oversized". A unit that is large for the load is more likely to switch off and on when demand is low, which installers call short-cycling (Energy Saving Trust).

This calculator leans the other way on purpose. It adds 10%, rounds up to the next 0.5 kW and never goes below 3 kW, so every figure it gives is at least 110% of its own heat loss estimate; in the tables above, where the minimum does not apply, they run from 110% to 127%. For a 50 m² flat built 2003 onwards at EPC C, the minimum gives 3.0 kW against 1,750 W, 171%. That suits a budget figure, not a design: the survey sizes to the measured load.

What flow temperature does a heat pump need, and will my radiators work?

Flow temperature is how hot the water leaving the heat pump is. The lower it can run while keeping the rooms warm, the less work the heat pump does. The standards treat 55°C as the ceiling:

  • Approved Document L (England): a new or fully replaced wet system is designed at 55°C or lower, or as low as possible where that is not feasible.
  • MIS 3005-D: avoid high-temperature heat pumps unless the home needs more than 55°C, and offer any higher design alongside one at 55°C or lower, with the difference in efficiency explained.
  • MIS 3005-D, for hybrids: the heat pump alone covers at least 55% of the heat load, rated at 55°C flow.

A radiator gives out less heat at a lower flow temperature, so some rooms may need more radiator surface. The Energy Saving Trust says you may need radiators with a higher surface area, that underfloor heating usually works well, and that the installer's efficiency estimate depends on the size of your radiators.

What does an MCS heat loss survey add?

This calculator multiplies floor area by an average W/m² for the home's age. A survey calculates your actual home, to BS EN 12831-1:2017 as MIS 3005-D requires:

  • Room by room, with inside temperatures no lower than 21°C for living and dining rooms, 18°C for bedrooms, halls and kitchens, and 22°C for bathrooms. MCS publishes a free Heat Load Calculator for installers that works this way.
  • Against a local outside temperature, not one UK figure: at the standard's 99% column, -1.7°C for London, -3.2°C for Birmingham, -3.5°C for Glasgow.
  • In writing before work starts: each room's heat loss in W/m², the design flow temperature, the emitter temperature for the worst-performing room, and the expected seasonal efficiency (SCoP).

A quote that names a kW size with no room-by-room calculation behind it has skipped the step the standard depends on.

Replacing an oil boiler in Northern Ireland

The heat pump is sized the same way; MIS 3005-D puts Belfast at -1.5°C at its 99% column. The difference is money: the Boiler Upgrade Scheme covers England and Wales only, and Northern Ireland has no equivalent heat pump grant open to every homeowner. See Northern Ireland energy grants.

How do you size an air-to-air heat pump?

An air-to-air heat pump warms room air through indoor units rather than heating water. MCS says certified systems must be optimised to heat your whole property, not for cooling, and Approved Document L (England) says the same of reversible systems. Most do not provide hot water (Energy Saving Trust). Use this calculator's heat loss as a whole-home starting point.

The Boiler Upgrade Scheme (England and Wales) sets £2,500 for an air-to-air heat pump in a home; air-to-air became eligible under the scheme's regulations on 28 April 2026 (SI 2026/390), but no installer is yet MCS-certified to fit one, so the grant cannot be claimed yet (Energy Saving Trust, 20 October 2026). The Energy Saving Trust reports that MCS expects certification before the end of 2026.

How this heat pump sizing calculator works

Every kW figure on this page, in the tool and the tables, comes from one formula:

  • Heat loss (W) = W/m² for the age band × floor area × EPC factor.
  • Capacity (kW) = heat loss ÷ 1,000 × 1.1, rounded up to the next 0.5 kW, with a minimum of 3 kW.
  • W/m² by age band: Pre-1900 100; 1900–1929 95; 1930–1949 80; 1950–1966 75; 1967–1975 65; 1976–1982 55; 1983–1990 50; 1991–2002 45; 2003 onwards 35.
  • EPC factor: A 0.75; B 0.85; C 1.00; D 1.10; E 1.20; F 1.30; G 1.40. "I don't know" uses 1.10, the same as D.

Two worked examples. A 90 m² home built 1930–1949 at EPC D: 80 × 90 × 1.10 = 7,920 W; × 1.1 = 8.712 kW; rounded up, 9.0 kW. A 50 m² flat built 2003 onwards at EPC C: 35 × 50 × 1.00 = 1,750 W; × 1.1 = 1.925 kW; rounded up, 2.0 kW, which the 3 kW minimum lifts to 3.0 kW.

The W/m² bands and EPC factors are this calculator's own estimates for typical homes, not figures from MIS 3005-D or BS EN 12831; they give a budget figure before a survey. Survey method: MIS 3005-D and the MCS Heat Load Calculator. Installed costs and the install mix: Department for Energy Security and Net Zero, Boiler Upgrade Scheme (BUS) monthly statistics, England and Wales: September 2026; later releases are in the Boiler Upgrade Scheme statistics collection.

Last reviewed: . Cost figures: Boiler Upgrade Scheme (BUS) monthly statistics, England and Wales: September 2026 (Department for Energy Security and Net Zero, published 29 October 2026).

Frequently asked questions

What size heat pump do I need for a UK home?

Most UK homes need 4–12 kW of air source heat pump capacity. A modern three-bedroom semi at ~90 m² sizes around 3.5–4.5 kW. A pre-1930 four-bedroom detached at ~140 m² with EPC D usually needs 16.5–17 kW. The calculator above sizes from your property age, floor area, and current EPC band.

How much does a heat pump cost in the UK?

Under the Boiler Upgrade Scheme the median installed cost of an air source heat pump was £12,826 in 2026 Q3 (July to September), with the middle half of installs between £10,717 and £15,461 before the grant. Cost rises with size: the median for a 6-8 kW install in 2025/26 was £12,164, and for 10-12 kW £13,948. The £7,500 grant takes the middle half to £3,217-£7,961. Source: Boiler Upgrade Scheme (BUS) monthly statistics, England and Wales: September 2026 (Department for Energy Security and Net Zero, published 29 October 2026). The grant covers eligible installs in England and Wales (you own the property, you are replacing a fossil fuel or electric heating system, and an MCS-certified installer does the work). Off the gas grid and replacing oil or LPG, the grant for an air source or ground source heat pump is £9,000 for applications made from ${upliftStartText} to ${upliftEndText}. A valid EPC is no longer a condition — that requirement was removed on 28 April 2026.

Am I eligible for the £7,500 Boiler Upgrade Scheme?

The scheme covers England and Wales. You need to own the property, be replacing a fossil fuel or electric heating system, and have the install done by an MCS-certified installer; social housing is excluded. The grant is £7,500 for an air source or ground source heat pump, or £9,000 if the property has no mains gas connection and is heated by oil or LPG (applications made from 21 July 2026 to 31 March 2027). There is no EPC requirement — it was removed on 28 April 2026. Applications close 31 December 2029. Properties on the gas grid swapping to a heat pump are eligible.

Do heat pumps work in older UK homes?

Yes — heat pumps work in any UK home, including pre-1900 properties. The size of the unit and the level of fabric upgrade needed (insulation, glazing) vary by property age. Pre-1930 homes typically need a larger heat pump (around 8.5–17 kW at EPC D, from ~70 m² to ~140 m²) and benefit most from cavity or solid wall insulation upgrades alongside the install.

Does EPC band affect heat pump sizing?

Yes. A property with EPC C needs a smaller heat pump than the same property at EPC E because heat loss is lower. The calculator applies an EPC band modifier to the baseline age-based heat loss figure. Improving the EPC before installing a heat pump (better insulation, double glazing) reduces the unit size needed and improves running costs.

Is it bad to oversize a heat pump?

Beyond a small margin, yes. The MCS design standard asks for at least 100% of the calculated heat load, and in England Approved Document L says systems should not be significantly oversized. An oversized unit is more likely to switch off and on (short-cycling) when demand is low (Energy Saving Trust). This calculator adds 10% and never goes below 3 kW, so treat its figure as a budget estimate.

What flow temperature should a heat pump run at?

As low as the home allows. In England, Approved Document L asks for new or fully replaced wet systems to be designed at 55°C or lower. The MCS design standard says any design above 55°C should come with an alternative at 55°C or lower, with the difference in efficiency explained. Your installer gives you the design flow temperature in writing.

Do I need bigger radiators for a heat pump?

Possibly, in some rooms. The Energy Saving Trust says you may need radiators with a higher surface area, and that underfloor heating usually works well. The survey's room-by-room heat losses show which rooms need it.

Can I get the £2,500 air-to-air heat pump grant now?

Not yet. The Boiler Upgrade Scheme (England and Wales) sets £2,500 for an air-to-air heat pump in a home, but the grant needs an MCS-certified installer and none is yet certified for air-to-air (Energy Saving Trust, 20 October 2026).

Is there a heat pump grant in Northern Ireland?

Not a universal one. The Boiler Upgrade Scheme covers England and Wales only, and Northern Ireland has no equivalent heat pump grant open to every homeowner; support there is limited and priority-led. See Northern Ireland energy grants.